Refrigeration installation and alteration permits
May 29, 2023
We propose changing the description for Refrigeration Installation or Alteration Permits to clarify which type of systems and equipment require an installation permit and which require a decal. This proposed change clarifies that refrigeration systems and equipment of any size that do not meet the existing criteria for the installation permit decal program are to use the standard Refrigeration Installation or Alteration Permit fee. Only certified refrigeration equipment within the parameters outlined in the fee schedule can use the Refrigeration Installation Permit Decal fee.
Current wording in fee schedule (2023) |
Proposed change (2024) |
|
Refrigeration Installation or Alteration Permit: ($)
Note 1: Permit fee does not include inspection. Inspection hours will be charged in addition. |
Refrigeration Installation or Alteration Permit: ($)
Note 1: Permit fee does not include inspection. Inspection hours will be charged in addition. |
|
Refrigeration Installation or Alteration Permit: ($) (Decal applicable for all refrigeration equipment conforming to CSA B52 section 5.2 within the following parameters)
Note 1: The refrigeration contractor is to supply a declaration of installation that includes details of:
Note 2: A decal is to be applied to the unit Note 3: An assessment will be carried out to determine if an inspection is required *This became effective on April 15, 2013 |
Refrigeration Installation Permit Decal: ($) (Decal applicable for all refrigeration equipment conforming to CSA B52 section 5.2 within the following parameters)
Note 1: The refrigeration contractor is to supply a declaration of installation that includes details of:
Note 2: A decal is to be applied to the unit Note 3: An assessment will be carried out to determine if an inspection is required Note 4: Permit fee does not include inspection. Inspection hours will be charged in addition. |
This proposed change to the fee schedule clarifies that equipment and systems that do not conform to CSA B52 section 5.2 with prime mover nameplate rating of less than 125kW/25kW fall under an installation permit. This includes shop-assembled refrigeration skids, smaller field-erected refrigeration systems, and other refrigeration systems and equipment that do not conform to CSA B52 section 5.2. Equipment and systems that are not certified by a certification agency and do not conform to CSA B52 Section 5.2 are required to have their designs registered through Technical Safety BC’s Design Registration process.
Refrigerant group |
Prime mover rating |
Certified and conforms to CSA B52 section 5.2? |
Permit type required |
A1 |
Under 5kW |
N/A |
None (exempt) |
5kW-125kW |
Yes |
Decal |
|
No |
Installation permit |
||
More than 125kW |
N/A |
Installation permit |
|
A2 |
Under 5kW |
N/A |
None (exempt) |
5kW-125kW |
Yes |
Decal |
|
No |
Installation permit |
||
More than 125kW |
N/A |
Installation permit |
|
A3 |
Under 5kW |
N/A |
None (exempt) |
5kW-25kW |
Yes |
Decal |
|
5kW-25kW |
No |
Installation permit |
|
More than 25kW |
N/A |
Installation permit |
|
B1 |
Under 5kW |
N/A |
None (exempt) |
5kW-125kW |
Yes |
Decal |
|
No |
Installation permit |
||
More than 125kW |
N/A |
Installation permit |
|
B2 |
Under 5kW |
N/A |
None (exempt) |
5kW-25kW |
Yes |
Decal |
|
5kW-25kW |
No |
Installation permit |
|
More than 25kW |
N/A |
Installation permit |
|
B3 |
Under 5kW |
N/A |
None (exempt) |
5kW-25kW |
Yes |
Decal |
|
5kW-25kW |
No |
Installation permit |
|
More than 25kW |
N/A |
Installation permit |
Note: In addition to the exemptions listed above, the following types of refrigeration systems are exempt from the application of the Power Engineers, Boiler, Pressure Vessel and Refrigeration Safety Regulation:
- Refrigeration systems that do not contain toxic or flammable contents and are installed in a building containing four or fewer self-contained residential units
- Refrigeration systems used for air conditioning or refrigerated compartments on railway cars, motor vehicles, motor-drawn vehicles, aircraft or ships